Explainer · The limit

800 VA explained: why a 1,260 W kit is still within the limit

The 800 VA figure is a cap on the inverter's AC apparent output, not on the panels. Panels are rated in DC watts under laboratory conditions they almost never see in Great Britain, so a kit deliberately carries more DC capacity than the inverter can pass — 515 W to 1,260 W behind a single 799 VA microinverter. The inverter simply clips the rare peaks and runs closer to its ceiling for far more of the day.

Last reviewed: 13 August 2026

Share
The cap
800 VA apparent output
Our inverter
799 VA continuous
Panel capacity
515W – 1,260W DC
Framework live
27 August 2026

Two different numbers, two different jobs

Every plug-in solar kit is described with two figures, and confusing them is the single most common misunderstanding in the category.

DC watts describe the panels. It is a laboratory rating measured at standard test conditions: 1,000 watts of irradiance per square metre, a cell temperature of 25°C, and a defined light spectrum. A British garden delivers that combination for a handful of hours a year, if at all.

AC volt-amperes describe the inverter — the box that converts panel output into mains-compatible electricity and pushes it through your plug. This is the number the framework regulates, because it is the only number the electricity network ever sees.

Why kits deliberately carry more panel than that

If panels reliably produced their rated output, matching 800 W of panel to an 800 VA inverter would be correct. They do not. A south-facing British array spends most of its generating hours well below its rating — cloud, low sun angle, temperature and dirt all take their share.

Oversizing the DC array fixes the shape of the day rather than the height of the peak. More panel area means the inverter reaches useful output earlier in the morning, holds it later into the evening, and produces something worthwhile on grey days that would otherwise be near-worthless. The trade is that on a handful of bright, cool afternoons the panels could have produced more than 799 VA — and that surplus is simply not converted.

What clipping actually costs

Our savings model applies a cautious flat annual derate wherever DC capacity exceeds the AC ceiling, rather than pretending oversizing is free.

Clipping derate applied across the current range
KitDC capacityDC:AC ratioAnnual derate appliedRRP
SocketPower Pro Compact 515W515W0.64:1None£599
SocketPower Pro Duo 890W890W1.11:1−1%£999
SocketPower Pro Plus 1030W1030W1.29:1−3%£1,099
SocketPower Pro Max 1260W1260W1.58:1−7%£1,199

Even after that derate, the larger kits generate more each year than the smaller ones. What they do not do is produce a higher peak — the ceiling is identical across the range.

Volt-amperes versus watts, briefly

Watts measure real power — the part that does work. Volt-amperes measure apparent power, the product of voltage and current regardless of how well they line up in phase. Network operators regulate apparent power because current is what heats cables, whether or not it is doing useful work.

A modern grid-tied microinverter runs at a power factor close to unity, so 799 VA and roughly 799 W amount to much the same thing in practice. The framework is written in VA because that is the engineering unit that matters at the connection point.

What this means when you are comparing kits

A seller advertising a "1,000 W plug-in solar kit" is describing panels. That is fine, provided the inverter is inside the limit and the product is supplied as a complete tested device. What is not fine is a kit whose inverter exceeds 800 VA, a kit assembled from separately-bought parts, or a substituted plug or lead.

When you compare, read the inverter specification and not the headline wattage. Our buyer's guide to comparing kits sets out the rest of the checks.

Common questions

Sources

Editorial note · Last reviewed 13 August 2026

Written and reviewed by SocketPower, a trading name of Storm Renewables Ltd (SC802881). This guide is general information about plug-in solar in Great Britain, not electrical design advice for your property. Always follow the instructions supplied with your product and use a qualified electrician for any work on your fixed wiring.

Keep reading

Plug-in solar in Great Britain: the framework covers single-phase solar PV with a maximum inverter apparent output of 800 VA, and SocketPower devices are limited to 799 VA continuous AC output. Plug-in batteries and battery-integrated devices are outside the framework and are not sold by SocketPower. The current G98 arrangements allow one plug-in solar device per household, and network notification remains required — SocketPower handles the applicable notification for kits bought from us. This framework applies in Great Britain from 27 August 2026 and not in Northern Ireland. Always follow the instructions supplied with your product, check that your socket and circuit are suitable, never use extension leads, multiway adaptors, travel adaptors or plug-in RCD adaptors, and obtain any permissions you need before installing.